Skip to main content
NSNC0051PHBESP · Grid-Scale ESS

3,727kWh
Power Plant.

A full megawatt-hour of energy storage in a single 20-ft container. Ready to connect to medium-voltage infrastructure and begin delivering grid services the day it arrives.

3,727kWh
Usable energy
1.86MW
AC output power
91%
Round-trip efficiency
20ft
ISO container
Request Engineering Consultation All ESS Products
Neutron Systems / ESS / Power Plant Container

Everything inside.
One delivery.

The NSNC0051PHBESP is a fully factory-assembled and tested system. Every component — batteries, PCS, BMS, HVAC, fire suppression, and monitoring — is installed and commissioned before it leaves the factory.

Grid-Scale ESS NSNC0051PHBESP 20ft container
  • LFP battery racks — pre-wired and balanced
  • Integrated 1.86 MW PCS (Power Conversion System)
  • Hierarchical BMS — cell to system level
  • Active liquid cooling for battery modules
  • Precision air conditioning — HVAC system
  • Multi-zone smoke and thermal fire detection
  • Integrated aerosol/gas fire suppression
  • Factory acceptance testing (FAT) before shipping
  • MV transformer integration (optional)
IEC 62619 UN38.3 CE G99 (UK) ISO Container

Full Specifications

Battery System
Cell ChemistryLFP (LiFePO₄) prismatic
Total Nominal Capacity4,096 kWh
Usable Capacity3,727 kWh (at 25°C)
System Voltage1,500 V DC (nominal)
Depth of Discharge91%
Round-trip Efficiency≥ 91%
Self-discharge Rate< 2% per month
Cycle Life10,000+ cycles at 80% DoD
Calendar Life20 years
Power Conversion System
AC Output Power1,860 kW (1.86 MW)
AC Output Voltage10 kV MV or 400 V LV (configurable)
AC Frequency50 / 60 Hz
AC Charging PowerUp to 1.86 MW
Power Factor≥ 0.99 (adjustable ±0.9)
THDi≤ 3%
PCS Efficiency≥ 98%
Reactive Power ControlYes — 4-quadrant operation
Grid Services Capability
Frequency ResponseFFR, DCR, DC response (per NGESO specs)
Ramp RateFull power in < 150 ms
Voltage SupportReactive power injection / absorption
Black StartConfigurable (grid-forming mode)
Island ModeYes — automatic and manual
V2G IntegrationModbus / CAN interface available
BMS
Architecture3-level: cell module BMS → rack BMS → system BMS
SOC Accuracy± 1.5%
SOH MonitoringContinuous — per cell
Cell BalancingActive balancing ≤ 5 mV deviation
Fault DetectionInsulation resistance, arc, thermal runaway pre-warning
Communications & EMS
EMS IntegrationNeutron Grid EMS V2.0
SCADA InterfaceIEC 61850, DNP3, Modbus TCP
Grid Operator InterfaceEMS API, real-time telemetry
Data Resolution100 ms telemetry for grid services
Remote Access4G LTE primary, Ethernet secondary
CybersecurityIEC 62351 compliant, TLS 1.3
Safety & Fire Protection
Fire DetectionMulti-zone optical smoke + thermal imaging
Fire SuppressionFM200 gas + aerosol system (zoned)
Emergency ShutdownRemote ESD + local manual
Explosion ReliefPressure relief vents — all zones
Safety StandardsIEC 62619, EN 62485, NFPA 855
Grid DisconnectFast-acting DC circuit breakers, MV switch
Physical & Environmental
Container Standard20-ft ISO 668 standard
Dimensions6,058 × 2,438 × 2,591 mm
Weight (loaded)~28,000 kg
Thermal ManagementActive liquid cooling (battery) + precision HVAC
Operating Temperature−20°C to +50°C (ambient)
Humidity5–95% non-condensing
Seismic RatingZone 4 (IBC 2018)
Altitude≤ 2,000 m
EnclosureIP54 (all access points)
Noise≤ 75 dB(A) at 1 m (full load)
CertificationsCE, IEC 62619, UN38.3, G99, IEC 61850
Warranty10 years / 6,000 cycles — capacity guarantee
Integration
EMS Platform
Neutron Grid EMS V2.0
Peak shaving, arbitrage, grid services
Protocols
IEC 61850 / DNP3 / Modbus
SCADA / EMS / Grid operator
Delivery lead time
12–16 weeks from order (FOB)
FAT included. Site commissioning available.
Request Consultation Download Technical Datasheet
Modular Grid ESS 232 kWh Power Plant

232 kWh
Power Plant

The 232 kWh Power Plant is a smaller-format grid-storage system — deployable by fork truck or crane, without specialist container-handling equipment. Stack multiple units in parallel for scalable grid storage.

Usable Capacity232 kWh
ChemistryLFP (LiFePO₄)
AC Output Power100 kW
AC Output Voltage400 V, 3-phase
Round-trip Efficiency≥ 90%
Cycle Life10,000+ cycles
Island ModeYes
EMS IntegrationNeutron Grid EMS V2.0
Fire SuppressionIntegrated aerosol system
CertificationsCE, IEC 62619
Warranty10 years
ScalabilityN × 232 kWh in parallel
Request Quote

Ready to design your grid storage project?

Our energy engineering team provides full project support — from load analysis to grid connection application.

Request Consultation Explore Grid EMS

Let's talk.

Product enquiries, project scoping, and partnership opportunities. Our engineering team responds within one business day.

Email
info@neutron-systems.com
Address

9 Mallow Street, London, EC1Y 8RQ
United Kingdom

Follow us